Integration Of An Rtd-Unit Ethernet (Tr1200 Ip) - Siemens SIPROTEC 5 Manual

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Function-Group Types
6.5 Function-Group Type Analog Units
[scauser6-190214-01, 1, en_US]
Figure 6-64
Now, set the channel number over which the SUP protocol runs. In addition, set the slave address of the RTD
box. This address must be set with the same value in the RTD box (refer to the following figure).
The following device configuration must be set on the TR1200 RTD unit when the RTD unit is used for the first
time:
Bus protocol: mod
Device address: 1
Baud rate: 9600
Parity: no
[scauser7-220114-01-DE, 1, en_US]
Figure 6-65
Finally, load the configuration in the device.
6.5.9.2

Integration of an RTD-Unit Ethernet (TR1200 IP)

Device Configuration
In the DIGSI, insert an Ethernet module into the provided slot, thus, adding the module to the device configu-
ration.
Figure 6-66
natively, you can also use the integrated Ethernet interface Port J.
208
Analog-Unit Instance
Setting the Port, Channel Number, and Slave Address
displays the available slots in the base module or on the expansion module CB 202. Alter-
SIPROTEC 5, Fault Recorder, Manual