Settings; Information List - Siemens SIPROTEC 5 Manual

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Fault Recorder
7.6 Measurands and Recorder Routing Functions
The procedure is described in chapter
the DIGSI Help.
Parameter: Tol. trend frequency
Default setting (_:15241:101) Tol. trend frequency = 0.200 %
Using the parameter Tol. trend frequency, you set the tolerance range for the frequency measured
value at which a new RMS value is recorded following an exceedance.
The setting value refers to the rated frequency set as a parameter.
Parameter: Tol. trend voltage
Default setting (_:15241:102) Tol. trend voltage = 2.000 %
Using the parameter Tol. trend voltage, you set the tolerance range for the voltage measured value at
which a new RMS value is recorded following an exceedance.
The setting value refers to the rated voltage set as a parameter.
7.6.4.4

Settings

Addr.
General
_:15241:101
_:15241:102
7.6.4.5

Information List

Frequency
No.
Routing f
_:301
Current
No.
Routing I
_:300
_:301
_:302
_:303
_:304
_:305
_:306
Voltage
No.
Routing I
_:300
_:301
358
7.1.2 Step 1: Creating a New Project and Adding a New Device
Parameter
C
General:Tol. trend
frequency
General:Tol. trend
voltage
Information
Routing f:f
Information
Routing I:Iph rms
Routing I:IN rms
Routing I:Iph fd.
Routing I:IN fd.
Routing I:I0
Routing I:I1
Routing I:I2
Information
Routing V:Vph rms
Routing V:Vpp rms
Setting Options
0.010 % to 1.000 %
0.100 % to 5.000 %
Data Class
(Type)
MV
Data Class
(Type)
WYE
MV
WYE
CMV
CMV
CMV
CMV
Data Class
(Type)
WYE
DEL
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
and in
Default Setting
0.200 %
2.000 %
Type
O
Type
O
O
O
O
O
O
O
Type
O
O

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siemens 7ke85

Table of Contents