Siemens SIPROTEC 5 Manual page 325

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Addr.
_:9751:124
_:9751:125
_:9751:126
_:9751:115
dM/dt drop (/Filter time)
_:9751:104
_:9751:108
_:9751:127
_:9751:128
_:9751:129
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Parameter
C
Trig. I fund 1:+dM/dt phs
1 A @ 100 Irated 0.030 A to 100.000 A
A
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Trig. I fund 1:+dM/dt phs
1 A @ 100 Irated 0.030 A to 100.000 A
B
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Trig. I fund 1:+dM/dt phs
1 A @ 100 Irated 0.030 A to 100.000 A
C
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Trig. I fund 1:+dM/dt
hysteresis
Trig. I fund 1:-dM/dt
active
Trig. I fund 1:-dM/dt
1 A @ 100 Irated 0.030 A to 100.000 A
(Non-phs sel.)
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Trig. I fund 1:-dM/dt phs
1 A @ 100 Irated 0.030 A to 100.000 A
A
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Trig. I fund 1:-dM/dt phs
1 A @ 100 Irated 0.030 A to 100.000 A
B
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Trig. I fund 1:-dM/dt phs
1 A @ 100 Irated 0.030 A to 100.000 A
C
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
7.5 Trigger Functions 3-Phase
Setting Options
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.900 p.u. to 0.990 p.u.
no
yes
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
Fault Recorder
Default Setting
0.300 A
1.50 A
0.300 A
1.50 A
0.300 A
1.500 A
0.300 A
1.50 A
0.300 A
1.50 A
0.300 A
1.500 A
0.300 A
1.50 A
0.300 A
1.50 A
0.300 A
1.500 A
0.980 p.u.
no
0.300 A
1.50 A
0.300 A
1.50 A
0.300 A
1.500 A
0.300 A
1.50 A
0.300 A
1.50 A
0.300 A
1.500 A
0.300 A
1.50 A
0.300 A
1.50 A
0.300 A
1.500 A
0.300 A
1.50 A
0.300 A
1.50 A
0.300 A
1.500 A
325