Siemens SIPROTEC 5 Manual page 99

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

[scugrsek-280113-01.tif, 1, en_US]
Figure 3-48
Threshold-Value Setting in an Example of the Current Transformer
If you only want to work in the secondary view, DIGSI 5 supports you if the transformer ratio changes during
the project phase.
In the example the following parameters are set according to the current transformer ratio of 1000 A/1 A . The
parameter dM/dt drop (/Filter time) has a setting value of 0.300 A (see the following image).
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Example for the Threshold Value of the Voltage Trigger Tripping Stage (Edit Mode: Secondary)
3.7 General Notes for Setting the Threshold Value of Trigger Functions
System Functions
99