Defect Severity 2 - Siemens SIPROTEC 5 Manual

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Indication
Power-system data:meas. point I-3ph:superv.
Phsseq.I:
(_:71) Failure
Power-system data:meas. point I-3ph:superv.
Sum I
(_:71) Failure
Power-system data:meas. point
I-3ph:superv.ADC sum.I:
(_:71) Failure
Power-system data:meas. point V-3ph:
Volt.Trans.Cir.B:
(_:500) >Open
Power-system data:meas. point V-3ph:
Superv. bal. V:
(_:71) Failure
Power-system data:meas. point V-3ph:
Superv. Phsseq.V:
(_:71) Failure
Power-system data:meas. point V-3ph:
Superv. of Sum V:
(_:71) Failure

Defect Severity 2

8.8.3
Faults of defect severity 2 are fatal device faults that lead to an immediate restart of the device (reset).
This occurs when the device data is corrupted (for example, RAM memory), if a restart prevents restoration of
data consistency. The device goes briefly out of operation, a failure is avoided.
Life contact
Red error LED
NOTE
i
i
If the fault of defect severity 2 has not be been removed after 3 unsuccessful restarts (reset), the fault is
automatically assigned to defect severity 3. The device will automatically turn to the fallback mode.
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Type
SPS
SPS
SPS
SPS
SPS
SPS
SPS
Is terminated during the restart
Is activated during the restart
8.8 Error Responses and Corrective Measures
Group
Explanation
Warning
Failure of the current phase-rotation
CFC
supervision (see chap.
of Functions
)
Failure of the current sum (see chap.
CFC
8.3.7.1 Overview of Functions
Failure of the quick current sum (see
CFC
chap.
8.4.2.1 Overview of
The failure indication indicates a fault in
the analog-digital converter at the
power input.
Check the exterior wiring.
If the fault is not remedied, contact
the Customer Support Center.
Quality: The internally managed current
measured values are marked with the
invalid quality attribute.
Blocking: The protection functions
based on current measurement are
blocked.
Voltage-transformer circuit breaker is
CFC
open.
Blocking: Appropriate functions are
either blocked definitely or the blocking
can be set individually.
Failure of the voltage balance (see chap.
CFC
8.3.2.1 Overview of Functions
Failure of the voltage phase-rotation
CFC
supervision (see chap.
of Functions
)
Failure of the voltage sum (see chap.
CFC
8.3.3.1 Overview of Functions
Supervision Functions
8.3.8.1 Overview
)
Functions)
)
8.3.4.1 Overview
)
405