Settings; Information List - Siemens SIPROTEC 5 Manual

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Function-Group Types
6.4 Function-Group Type Phasor Measurement Unit (PMU)
Parameter: Only positive sequence
Default setting (_:10621:103) Only positive sequence = no
With the parameter Only positive sequence, you set whether the positive-sequence system is to be
transmitted instead of 3 individual synchrophasors in the case of 3-phase measuring points. The setting you
make here is then valid for all PMUs with 3-phase measuring points.
Parameter: Class
Default setting (_:10621:101) Class = Class P
With the setting Class, you set which performance class is used for the calculation of the measured values.
Class P is the standard case for PMUs. In this case, filters are used that are suitable for a short response time
and therefore are well suited for recording dynamic processes. Class M is conceived for applications that are
unfavorably affected by alias effects and in which short response times are not relevant.
Parameter: Port
This parameter cannot be set because the Port results from the physical position where the corresponding
communication module is inserted.

Settings

6.4.9
Addr.
Func. settings
_:10621:1
_:10621:101
_:10621:102
_:10621:103

Information List

6.4.10
No.
General
_:10621:52
_:10621:53
170
Parameter
Func. settings:Mode
Func. settings:Class
Func. settings:Reporting
rate
Func. settings:Only positive
sequence
Information
Func. settings:Behavior
Func. settings:Health
C
Setting Options
off
on
test
Class P
Class M
1 frame/s
5 frames/s
6 frames/s
10 frames/s
12 frames/s
15 frames/s
20 frames/s
25 frames/s
30 frames/s
50 frames/s
60 frames/s
100 frames/s
120 frames/s
no
yes
Default Setting
on
Class P
10 frames/s
no
Data Class
Type
(Type)
ENS
O
ENS
O
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017