Settings - Siemens SIPROTEC 5 Manual

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Parameter: dM/dt Rise Active - dM/dt Rise (/Filter Time) - dM/dt Rise Hysteresis - Filter Time
Default setting (_:9871:103) dM/dt rise active = no
Default setting (_:9871:107) dM/dt rise (/Filter time) = 0.300 A
Default setting (_:9871:115) dM/dt rise hysteresis = 0.980 p.u.
Default setting (_:9871:112) Filter time = 2 periods
With the dM/dt rise active parameter, you activate the gradient trigger in order to monitor the positive
gradients of the current in the negative-sequence system using the set filtering time (input in periods).
Parameter Value
yes
no
The hysteresis is preset at the factory to 0.980 p.u. (equal to 2 %) of the parameter dM/dt rise (/Filter
time) and can be adjusted.
7.5.2.9

Settings

Addr.
General
_:9751:1
_:9751:117
_:9751:112
Max. trigger
_:9751:101
_:9751:105
_:9751:118
_:9751:119
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Description
The positive gradient of the current in the negative-sequence system is
monitored.
The positive gradient of the current in the negative-sequence system is not
monitored.
Parameter
C
Trig. I fund 1:Mode
Trig. I fund 1:Phase-
selective
Trig. I fund 1:Filter time
Trig. I fund 1:Max. active
Trig. I fund 1:Max. (Non-
1 A @ 100 Irated 0.030 A to 100.000 A
phs sel.)
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Trig. I fund 1:Max. phs A 1 A @ 100 Irated 0.030 A to 100.000 A
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Trig. I fund 1:Max. phs B 1 A @ 100 Irated 0.030 A to 100.000 A
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
7.5 Trigger Functions 3-Phase
Setting Options
off
on
test
no
yes
2 cycles to 250 cycles
no
yes
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
Fault Recorder
Default Setting
off
no
2 cycles
yes
1.200 A
6.00 A
1.200 A
6.00 A
1.200 A
6.000 A
1.200 A
6.00 A
1.200 A
6.00 A
1.200 A
6.000 A
1.200 A
6.00 A
1.200 A
6.00 A
1.200 A
6.000 A
323