Function-Group Types
6.5 Function-Group Type Analog Units
Addr.
_:13111:107
_:13111:104
_:13111:105
_:13111:109
_:13111:106
_:13111:110
6.5.3.8
Information List
No.
General
_:2311:53
_:2311:56
Channel 1
_:13111:53
_:13111:71
_:13111:301
_:13111:302
20-mA Unit Serial
6.5.4
6.5.4.1
Overview
The function 20-mA unit Serial:
•
Provides serial communications with a 20-mA unit via the Modbus protocol and records the values meas-
ured by the 20-mA unit
•
Transforms the measured 20-mA values into slowly changing process variables such as temperature or
gas pressure
•
Makes the recorded process tags available to CFC, GOOSE, protocols and the device display
•
Monitors communication with the 20-mA unit
The function 20-mA unit Serial is structured in the same way as the function 20-mA Unit Ether.. The mode of
operation is also identical. The only difference is that the measured values are transferred to the communica-
tion module via a serial connection instead of an Ethernet connection.
You can find more information in Chapter
6.5.4.2
Application and Setting Notes
Parameter: Port
•
Default setting (_:2311:103) Port = Port J
With the Port setting, you specify the slot for the communication module that will be used for the connection
with an external 20-mA unit.
Parameter: Channel number
•
Default setting (_:2311:105) Channel number = 1
180
Parameter
Channel 1:Range active
Channel 1:Conversion
factor
Channel 1:Upper limit
Channel 1:Upper limit -
Sensor
Channel 1:Lower limit
Channel 1:Lower limit -
Sensor
Information
General:Health
General:Failure
Channel 1:Health
Channel 1:Failure
Channel 1:20-mA output scale
Channel 1:20-mA output raw
6.5.3.2 Structure of the
C
Setting Options
•
0
•
1
1 to 1000000
0.00 mA to 20.00 mA
-1000000 to 1000000
0.00 mA to 20.00 mA
-1000000 to 1000000
Function.
Default Setting
false
100
20.00 mA
100
4.00 mA
100
Data Class
Type
(Type)
ENS
O
SPS
O
ENS
O
SPS
O
MV
O
MV
O
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017