tively. The magnitude correction may be required for highly precise measurements. Use a comparison meas-
urement to determine the setting value (for example, with a high-precision measuring-voltage transformer). If
a primary correction is not necessary, retain the default setting.
NOTE
i
i
The Magnitude correction parameter has nothing to do with the internal adjustment of the input
circuit.
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
5.5 Application and Setting Notes for Measuring Point Current 1-Phase (I-1ph)
Power-System Data
117