Settings - Siemens SIPROTEC 5 Manual

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

[sctimedg-220415, 1, en_US]
Figure 3-33
For every time source, you see the following:
Last received time (with date)
Receipt time of the last received time telegram
Configured type of timer
Indication of timer outage or failure
Whether the device time is currently synchronized from the time source
The lower section displays the device time, which is continuously updated. If the internal device time and the
infeed time source were synchronous at the time of telegram receipt, both displayed times are identical.
NOTE
i
i
All times displayed (also the time source) take into consideration the local time settings (zone and daylight
saving time of the device) in the form of a numerical offset for UTC (universal time).

Settings

3.4.4
Addr.
Time sync.
_:102
_:103
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Time Information in DIGSI
Parameter
Time sync.:Time source
1
Time sync.:Time source
1 port
C
Setting Options
none
IRIG-B
DCF77
PI
SNTP
IEC 60870-5-103
PROFIBUS DP
Modbus
DNP3
IEEE 1588
IEC 60870-5-104
port J
port F
port E
port P
port N
port G
System Functions
3.4 Date and Time Synchronization
Default Setting
none
85