Addr.
_:9781:121
_:9781:122
_:9781:123
_:9781:114
dM/dt rise (/Filter time)
_:9781:103
_:9781:107
_:9781:124
_:9781:125
_:9781:126
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Parameter
C
Trig. I RMS 1:Min. phs A
1 A @ 100 Irated 0.030 A to 100.000 A
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Trig. I RMS 1:Min. phs B
1 A @ 100 Irated 0.030 A to 100.000 A
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Trig. I RMS 1:Min. phs C
1 A @ 100 Irated 0.030 A to 100.000 A
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Trig. I RMS 1:Min. hyste-
resis
Trig. I RMS 1:+dM/dt
active
Trig. I RMS 1:+dM/dt
1 A @ 100 Irated 0.030 A to 100.000 A
(Non-phs sel.)
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Trig. I RMS 1:+dM/dt phs
1 A @ 100 Irated 0.030 A to 100.000 A
A
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Trig. I RMS 1:+dM/dt phs
1 A @ 100 Irated 0.030 A to 100.000 A
B
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Trig. I RMS 1:+dM/dt phs
1 A @ 100 Irated 0.030 A to 100.000 A
C
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
7.5 Trigger Functions 3-Phase
Setting Options
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
1.010 p.u. to 1.100 p.u.
no
yes
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
Fault Recorder
Default Setting
0.800 A
4.00 A
0.800 A
4.00 A
0.800 A
4.000 A
0.800 A
4.00 A
0.800 A
4.00 A
0.800 A
4.000 A
0.800 A
4.00 A
0.800 A
4.00 A
0.800 A
4.000 A
1.020 p.u.
no
0.300 A
1.50 A
0.300 A
1.50 A
0.300 A
1.500 A
0.300 A
1.50 A
0.300 A
1.50 A
0.300 A
1.500 A
0.300 A
1.50 A
0.300 A
1.50 A
0.300 A
1.500 A
0.300 A
1.50 A
0.300 A
1.50 A
0.300 A
1.500 A
327