Application And Setting Notes, Trigger Power Swing - Siemens SIPROTEC 5 Manual

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

[dw_powerswing_center, 1, en_US]
Figure 7-69
Power-swing detection operates on a phase-segregated basis in the event of power-swing currents ≥ 10 % of
the rated current and power-swing frequencies between 0.1 Hz and 8 Hz.
7.5.4.8

Application and Setting Notes, Trigger Power Swing

Parameter: Mode
Default setting Mode = off
With the parameter Mode, you activate the trigger for normal operation (on) or the test mode (test).
Parameter Value
on
off
test
Parameters: X reach, R (ph-g), and R (ph-ph)
Default setting X reach = 100
Default setting R (ph-g) = 100
Default setting R (ph-ph) = 200
With the parameters X reach, R (ph-g), and R (ph-ph), you set the parameters of a power-swing
polygon within which power-swing-typical resistance changes cause triggering. Resistance changes outside
this polygon do not cause triggering. You can adapt the sensitivity of power-swing detection by changing the
default values (see the following calculation example).
Calculation Example:
If triggering occurs using the default settings even during non-critical power swings, for example, you can
adapt the sensitivity. This calculation example serves as orientation.
For a given line, the following data are known:
3-phase short-circuit current on the left line
3-phase short-circuit current on the right line
Line impedance
Primary rated voltage
Primary rated current
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Power-Swing Center
Description
The Trigger Psw # function block is activated and the power swing is moni-
tored according to the set trigger parameters.
The Trigger Psw # function block is deactivated.
The Trigger Psw # function block is activated for test purposes.
Fault Recorder
7.5 Trigger Functions 3-Phase
20 kA/-72°
12 kA/-83
(5.17 + 19.31i) Ω
110 kV
800 A