Fast-Scan Recorder; Overview Of Functions; Structure Of The Function; Function Description - Siemens SIPROTEC 5 Manual

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Fault Recorder
7.2 Function-Group Type Recorder

Fast-Scan Recorder

7.2.6
7.2.6.1

Overview of Functions

The Fast-scan recorder records individual current and voltage sampled values at a sampling rate that is high
enough for the display of network events and transients.
The fast-scan recorder records at least 1 s up to a maximum of 90 seconds. The sampled values (SAV) are
always routed automatically to the Fast-scan recorder.
The fault record generated contains the following information:
Pre-trigger time
Trigger point
Fault Recording
Trigger end mark (if a falling trigger is detected)
Post-trigger time (if a falling trigger is detected)
In addition, the cause that trips the trigger is saved.
7.2.6.2

Structure of the Function

The function Fast-scan recorder is preconfigured once at the factory. Within the Recorder function group,
the Fast -scan recorder can only be operated once.
[dwfast7k-161012-01.tif, 1, en_US]
Figure 7-23
7.2.6.3

Function Description

Logic
The following logic diagram shows the method of function of the fast-scan recorder.
[lofastsc-161012-01.tif, 1, en_US]
Figure 7-24
The function Fast-scan recorder records the following data:
Sampled values (SAV) of all analog inputs
Measured values calculated internally
Binary signals
236
Structure/Embedding of the Function
Logic Diagram of the Fast-Scan Recorder Function
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017