Cfc - Siemens SIPROTEC 5 Manual

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Technical Data

11.7 CFC

11.7
CFC
Typical response times and maximum number of ticks of the CFC task levels:
Task Level
Fast Event-Triggered
Event-Triggered
Interlocking
Measurement
The times describe the response time of a typical CFC chart at the respective task level. The maximum number
of ticks applies to a typical load for the device based on the application template Fault recorder N6: 1/1, 43
BI, 33 BO, 20I, 20V
The task level Measurement runs in cycles every 500 ms. All other task levels are event-triggered.
In order to estimate the tick consumption of a CFC chart, you can use the following formula:
T
= 5 ∙ n
chart
where:
n
Number of indications routed as input in the CFC chart
Inp
n
Number of indications routed as output in the CFC chart
Outp
T
101 Ticks in Fast Event-Triggered Level
TLev
104 Ticks in Event-Triggered Level
54 Ticks in Measurement Level
74 Ticks in Interlocking Level
T
Number of internal connections between 2 CFC blocks in one chart
int
T
Used ticks per CFC block (see Technical Data)
Block
Table 11-1
Element
ABS_D
ABS_R
ACOS_R
ADD_D4
ADD_R4
ADD_XMV
ALARM
AND_SPS
AND10
APC_DEF
APC_EXE
APC_INFO
ASIN_R
ATAN_R
BLINK
BOOL_CNT
BOOL_INT
BSC_DEF
BSC_EXE
BSC_INFO
448
Time (in ms)
< 1
<5 (<10 ms)
<5 (<10 ms)
250
+ 5 ∙ n
+ T
+ ∑
T
Inp
Outp
TLev
i
int
Ticks of the Individual CFC Blocks
+ ∑
T
j
Block
Ticks
2.3
1.5
6.9
3.4
3.3
6.4
1.8
1.1
2.9
1.2
1.0
3.9
1.3
1.2
1.3
2.0
1.5
1.3
1.1
2.7
Max. Number of Ticks CP300
1500
12 397
28 656 in total
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017