Siemens SIPROTEC 5 Manual page 191

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Parameter: Range active
Default setting (_:107) Range active = false
If you do not activate the Range active parameter, the function assumes a range of -20 mA to +20 mA or
-10 V to +10 V. The setting of the range for the scaled value then assumes a usable range of -20 mA to +20
mA or -10 V to +10 V.
If you activate theRange active parameter, then 4 additional parametersUpper limit, Upper limit
- SensorLower limit, and Lower limit - Sensor appear.
Note that this setting is activated by either placing, or not placing the relevant check mark in DIGSI (see
Figure
6-52).
Parameter: Conversion factor
Default setting (_:104) Conversion factor = 1.00
With the parameterConversion factor you can set the conversion factor for the measuring transducer.
Parameter: Upper limit, Upper limit - Sensor, Lower limit and Lower limit - Sensor
With the following parameters, you set the scaling of the measuring variables. By that, you can scale in an
application-specific way:
Default setting Upper limit = 20.00 mA
Default setting Upper limit - Sensor = 1.00
Default setting Lower limit = -20.00 mA
Default setting Lower limit - Sensor = 1.00
With these setting parameters, you set the operating range of the measuring transducer as well as the conver-
sion of the values transmitted to the sensor values. Harmonize the operating range of the measuring trans-
ducer with the transmitter of the sensor. Using the free scalability of the system, you can meet different
requirements. The following figure shows the setting parameters in general terms.
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Function-Group Types
6.5 Function-Group Type Analog Units
191