Siemens SIPROTEC 5 Manual page 38

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Basic Structure of the Function
2.3 Function Control
Table 2-5
Function State
Explanation
On
The function is activated and operates as defined. The prerequisite is that status of the function is OK.
Off
The function is turned off. It does not create any information. The status of a selected function always
has the value OK.
Test
The function is set into test mode. This state supports the commissioning. All outgoing information of
the function (indication and, if available, measured values) is provided with a test bit. This test bit
significantly influences the further processing of the information, depending on the target.
NOTE: The Test mode is not available for the continuous recorder.
Target of the Information
Buffer
Contact
Light-emitting diode (LED)
CFC
Protocol
Status (Health)
The status indicates whether a selected function is capable of its designated functionality. If so, the status is
OK . If, due to the device's state or problems within the device, the functionality is possible only to a limited
extent or not at all, the status will indicate
Internal self-supervision can cause the functions to assume the
tions). If a function assumes the
Only a few functions can signal the
toring and is - if available - described in the function description. If a function assumes the
will remain active, that is, the function can continue to work in a conditional manner and trip in the case of a
protection function.
Inactive
The indication
Inactive signals that a function is currently not working. The indication Inactive is gener-
ated in the following cases:
Function is switched off
Status of the function is in
Function is blocked by an input signal (see
38
Possible Function States
Processing
The indications are provided with the identification Test in the buffer.
An indication routed to contact is not triggering the contact.
An indication routed to the LED triggers the LED (normal processing)
Here, the behavior depends on the state of the CFC chart.
A CFC chart can be set to the test state only by switching the entire
device to test mode.
Indication and measured value are transmitted with set test bit,
provided that the protocol supports this functionality.
If an object is transmitted as a GOOSE indication, the test bit is set spon-
taneously and the GOOSE indication is transmitted immediately. The
receiver of the GOOSE indication is automatically notified of transmitter
test mode.
Alarm status, it is no longer active (indication inactive is generated).
Warning status. The Warning status results from function-specific moni-
Alarm state
CFC chart itself is not in test state:
The chart is not triggered by a status change of an information
with set test bit. The initial state of the information (state before
test bit was set) is not processed during execution of the chart.
CFC chart itself is in test state:
The chart continues to process the information (indication or
measured value) normally. The CFC outgoing information is
provided with a test bit. The definitions in this table apply to its
continued processing.
Warning (limited functionality) or Alarm (no functionality).
Alarm status (see chapter Supervision Func-
Figure
2-1)
Warning status, it
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017