Parameter Value
no
If the gradient trigger does not operate phase-selectively, the set threshold value of the parameter -dM/dt
(Non-phs sel.) applies to all phases.
If the gradient trigger operates phase-selectively, set the threshold values for the gradient trigger separately
for each phase. Then, the parameters -dM/dt phs A(AB), -dM/dt phs B(BC), and -dM/dt phs C(CA)
are effective.
The hysteresis is preset at the factory to 0.980 p.u. (equal to 2 %) of the parameter -dM/dt (Non-phs
sel.) and can be adjusted.
7.5.1.6

Application and Setting Notes - V0 Trigger (Zero-Sequence System)

Parameter: Mode
Default setting (_:9631:1) Mode = off
With the Mode parameter, you activate the trigger for normal operation (On) or the test mode (Test).
Parameter Value
on
off
test
Parameter: Max. Trigger Active/Max. Trigger/Max. Trigger Hysteresis
Default setting (_:9631:101) Max. trigger active = yes
Default setting (_:9631:105) Max. trigger = 69.284 V
Default setting (_:9631:113) Max. trigger hysteresis = 0.980 p.u.
With the Max. trigger active parameter, you activate the level trigger in order to monitor in the zero-
sequence system the voltage and to prevent it from exceeding the set values.
Parameter Value
yes
no
The hysteresis is preset at the factory to 0.980 p.u. (equal to 2 %) of the parameter Max. trigger and can
be adjusted.
Parameter: dM/dt Rise Active - dM/dt Rise (/Filter Time) - dM/dt Rise Hysteresis - Filter Time
Default setting (_:9631:103) dM/dt rise active = no
Default setting (_:9631:107) dM/dt rise (/Filter time) = 11.547 V
Default setting (_:9631:115) dM/dt rise hysteresis = 0.980 p.u.
Default setting (_:9631:112) Filter time = 2 periods
With the dM/dt rise active parameter, you activate the gradient trigger in order to monitor the positive
gradients of the voltage in the zero-sequence system using the set filtering time (input in periods).
Parameter Value
yes
no
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Description
The negative gradient of the RMS value of the voltage is not monitored.
Description
The function block V0 Trigger is activated and the voltage in the zero-
sequence system is monitored on the basis of the set trigger parameter.
The function block V0 Trigger is deactivated.
The function block V0 Trigger is activated for test purposes.
Description
The voltage in the zero-sequence system is monitored for overvoltage.
The voltage in the zero-sequence system is not monitored for overvoltage.
Description
The positive gradient of the voltage in the zero-sequence system is moni-
tored.
The positive gradient of the voltage in the zero-sequence system is not
monitored.
Fault Recorder