Fault Recorder
7.5 Trigger Functions 3-Phase
Calculation of the source impedances of the left and right side of the supplying line:
Z
= (1.1 • 110 kV) / (√3 • 20 kA) • e
s-b
Z
= (1.1 • 110 kV) / (√3 • 12 kA) • e
s-a
Calculation of the total impedances between the generators:
Z
= Z
+ Z
+ Z
Σ
s-a
s-b
Calculation of the distance to the power-swing center:
Z
= 0.5 • Z
Reach-A
Z
= 0.5 • Z
Reach-B
NOTE
i
i
The power-swing trigger starts operating at a minimum current of 10 % Irated. Power-swing detection
drops out once the current is below the minimum current. Power-swing frequencies between 0.1 Hz and
8 Hz are detected.
For the setting value X reach, use a safety margin of at least 20 %, yielding this result:
X reach = 1.2 • 8.5 Ω = 10.2 Ω.
Use the same setting value for R (ph-g).
Use double the value of X reach for R (ph-ph).
7.5.4.9

Settings

Addr.
Trigger Psum 1
_:9901:1
_:9901:111
_:9901:101
_:9901:105
_:9901:113
_:9901:102
_:9901:106
_:9901:114
_:9901:103
_:9901:107
_:9901:115
_:9901:104
344
i 72°
= 1.08 + 3.32i Ω
i 83°
= 0.71 + 5.77i Ω
= (1.08 + 3.32i + 0.71 + 5.77i + 5.17 + 19.31i) Ω = 6.96 + 28.41i Ω
line
- Z
= 0.5 • (6.96 + 28.41) - (0.71 + 5.77i) Ω = 2.77 + 8.44i Ω
Σ
s-a
- Z
= 0.5 • (6.96 + 28.41) - (1.08 + 3.32i) Ω = 2.40 + 10.88i Ω
Σ
s-a
Parameter
Trigger Psum 1:Mode
Trigger Psum 1:Power
direction
Trigger Psum 1:Max.
trigger active
Trigger Psum 1:Max.
trigger
Trigger Psum 1:Max.
trigger hysteresis
Trigger Psum 1:Min.
trigger active
Trigger Psum 1:Min.
trigger
Trigger Psum 1:Min.
trigger hysteresis
Trigger Psum 1:dM/dt
rise active
Trigger Psum 1:dM/dt
rise (/Filter time)
Trigger Psum 1:dM/dt
rise hysteresis
Trigger Psum 1:dM/dt
drop active
C
Setting Options
off
on
test
negative
positive
no
yes
1 A @ 100 Irated 0.36 Wto 6000.00 W
5 A @ 100 Irated 1.80 W to 300000.00 W
0.900 p.u. to 0.990 p.u.
no
yes
1 A @ 100 Irated 0.36 Wto 6000.00 W
5 A @ 100 Irated 1.80 W to 300000.00 W
1.010 p.u. to 1.100 p.u.
no
yes
1 A @ 100 Irated 0.36 Wto 6000.00 W
5 A @ 100 Irated 1.80 W to 300000.00 W
0.900 p.u. to 0.990 p.u.
no
yes
Default Setting
off
positive
yes
207.85 W
1039.23 W
0.980 p.u.
yes
138.56 W
692.82 W
1.020 p.u.
no
34.64 W
173.21 W
0.980 p.u.
no