Application And Setting Notes - Siemens SIPROTEC 5 Manual

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Application and Setting Notes

6.4.8
Time Synchronization
In order to ensure the time accuracy of the PMU, you must select IRIG-B as protocol for the GPS clock, see the
following figure. With other settings, the PMU function function group indicates that it is not time synchron-
ized.
[sc_setting time source_2014-09-09, 1, en_US]
Figure 6-30
To detect a lack of synchronization quickly, also set the waiting time for the failure indication of the loss of
time synchronization to the smallest possible value, thus to 1 s.
Parameter: Mode
Default setting (_:10621:1) Mode = on
Activate and deactivate the PMU or switch to Test mode via the parameter Mode. The possible setting values
are on, off and test. In Test mode, the PMU data is marked as invalid.
Parameter: Reporting rate
Default setting (_:10621:102) Reporting rate = 10 frames/s
With the parameter Reporting rate, you specify the number of telegrams that are compiled and sent to
the PDC per second.
NOTE
i
i
Different setting values are shown or hidden, depending on the rated frequency set.
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Setting Time Synchronization
6.4 Function-Group Type Phasor Measurement Unit (PMU)
Function-Group Types
169