Application And Setting Notes; Settings; Information List - Siemens SIPROTEC 5 Manual

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Supervision Functions
8.3 Supervision of the Secondary System
8.3.8.4

Application and Setting Notes

Parameter: Delay failure indication
Recommended setting value (_:6) Delay failure indication = 5.00 s
Set the Delay failure indication parameter so that overfunctions due to disturbing influences (such as
switching operations) are avoided. Siemens recommends using the default setting.
8.3.8.5

Settings

Addr.
Supv. ph.seq.I
_:1
_:6
8.3.8.6

Information List

No.
Supv. ph.seq.I
_:82
_:54
_:52
_:53
_:71
392
Parameter
Supv. ph.seq.I:Mode
Supv. ph.seq.I:Operate
delay
Information
Supv. ph.seq.I:>Block function
Supv. ph.seq.I:Inactive
Supv. ph.seq.I:Behavior
Supv. ph.seq.I:Health
Supv. ph.seq.I:Failure
C
Setting Options
off
on
test
0.00 s to 100.00 s
Default Setting
off
5.00 s
Data Class
Type
(Type)
SPS
I
SPS
O
ENS
O
ENS
O
SPS
O
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017