[scfastsc-270213-01.tif, 1, en_US]
Figure 7-11
Ensure the parameter Mode is activated.
•
Default setting (_:2731:1) Mode = on
When using the overlapping parameter Mode , the recorder is activated.
Parameter Value
Description
The recorder is activated.
on
The recorder is deactivated in different ways depending on the recorded type:
off
•
•
The recorder is activated for test purposes. In the test mode, the record is marked using the test
test
flag (true) (see the following figure).
NOTE
i
i
The test mode is not available for the continuous recorder and the trend recorder and applies only to the
fast-scan and slow-scan recorders.
[sctestfl-291012-01.tif, 1, en_US]
Figure 7-12
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Parameter Setting in the Example of the Fast-Scan Recorder
The fast-scan recorder and the slow-scan recorder are deactivated.
The continuous recorder and the trend recorder are deactivated, but continue to record time
jumps, modes on/off, as well as disconnection and recovery of supply voltage.
PQDif recordings are still generated, even though the continuous recorder and the trend
recorder are set to the mode off. It is recommended to delete the instance in case of long-
term non-use.
Fault Record with Activated Marking Test Record (Test Flag)
Fault Recorder
7.1 Introduction to DIGSI 5
223