Settings - Siemens SIPROTEC 5 Manual

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Supervision Functions
8.3 Supervision of the Secondary System
module. The binary inputs of the PS201 power-supply module permanently installed in the base module count
as the 2nd I/O module followed by additional I/O modules (3 to n) in the expansion boards of the device.
Parameter (Supervision Signal): Binary input
Default setting (_:105) Binary input = 1
Using the Binary input parameter, you specify the binary input responsible for the supervision of the
signaling voltage for the parameterized I/O module. The quality attribute of all other binary inputs for this
module are set to valid or invalid depending on the presence of the signaling voltage at the parameterized
binary input.
Parameter (Supervision Signal): Enable variable group
Default setting (_:102) Enable variable group = untrue
You can activate the parameter Enable variable group by placing the check mark. If you have not set
the check mark (default setting), only these 2 parameters are available for the configuration of the supervision
signal. If you have set the check mark, the parameter menu is extended by the areas Start supervision group
and End supervision group. You can then use that to carry out the grouping of binary inputs for supervision
groups explained in the function description.
Parameter (Start Supervision Group): I/O module ID
Default setting (_:106) I/O module ID = I/O module 1
Parameter I/O module ID is used to define the first I/O module that you want to assign to a supervision
group. As the counting of the I/O module starts in ascending order with the binary inputs of the base module,
this is the module with the lowest counter number that you can use for carrying out a grouping.
Parameter (Start Supervision Group): Binary input
Default setting (_:107) Binary input = 1
Parameter Binary input is used to define the lowest binary input for the first I/O module (see (_:106)
I/O module ID) that you want to assign to a supervision group.
Parameter (End Supervision Group): I/O module ID
Default setting (_:108) I/O module ID = I/O module 1
Parameter I/O module ID is used to define the last I/O module that you want to assign to a supervision
group. As the counting of the I/O module starts in ascending order with the binary inputs of the base module,
this is the module with the highest counter number that you can use for carrying out a grouping.
Parameter (End Supervision Group): Binary input
Default setting (_:109) Binary input = 1
Parameter Binary input is used to define the highest binary input for the last I/O module (see (_:108)
I/O module ID) that you want to assign to a supervision group.
8.3.1.5

Settings

Addr.
General
_:1
370
Parameter
C
Superv.Grp.#:Mode
Setting Options
off
on
test
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Default Setting
on