Power-System Data
5.8 Settings
Addr.
_:2311:105
_:2311:130
CT 1
_:3841:103
_:3841:117
Measuring Point V-3ph
Addr.
General
_:8911:101
_:8911:102
_:8911:103
_:8911:104
_:8911:106
_:8911:111
_:8911:130
VT 1
_:3811:103
_:3811:108
VT 2
_:3812:103
128
Parameter
C
General:Tracking
General:Measuring-point
ID
CT 1:Magnitude correc-
tion
CT 1:Phase
Parameter
C
VT 3-phase:Rated
primary voltage
VT 3-phase:Rated secon-
dary voltage
VT 3-phase:Matching
ratio Vph / VN
VT 3-phase:VT connec-
tion
VT 3-phase:Inverted
phases
VT 3-phase:Tracking
VT 3-phase:Measuring-
point ID
VT 1:Magnitude correc-
tion
VT 1:Phase
VT 2:Magnitude correc-
tion
Setting Options
•
inactive
•
active
0 to 100
0.010 to 10.000
•
I A
•
I B
•
I C
•
IN
•
INsens
•
Ix
Setting Options
0.200 kV to 1200.000 kV
80 V to 230 V
0.10 to 9.99
•
not assigned
•
3 ph-to-gnd volt. + VN
•
3 ph-to-gnd voltages
•
3 ph-to-ph volt. + VN
•
3 ph-to-ph voltages
•
none
•
AC
•
BC
•
AB
•
inactive
•
active
0 to 100
0.010 to 10.000
•
V A
•
V B
•
V C
•
V AB
•
V BC
•
V CA
•
VN
•
Vx
•
VCB
0.010 to 10.000
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Default Setting
inactive
0
1.000
Default Setting
400.000 kV
100 V
1.73
3 ph-to-gnd
volt. + VN
none
active
0
1.000
1.000