Defect Severity 4 (Group Alarm)

Errors of defect severity 4 are not device failures in the classical meaning. These errors do not affect the device
hardware and are not detected or reported by internal device supervision functions. The condition of the
defect severity 4 – the group alarm – is set user-specifically by the binary input signal
alarm . If the binary input signal is reset, the device is no longer in the Group alarm condition and all func-
tions return to the normal operating state.
If the group alarm is generated, the device reacts as follows:
The group indication
The life contact is terminated.
The red Error LED is activated.
All protection and automation functions are blocked.
The device remains in operation, does not carry out any restart (reset), and does not switch to the safe
condition (Fallback mode).
The signals managed internally are marked with the invalid quality attribute. Signals managed inter-
nally are, for example, measured values, binary input and output signals, GOOSE and CFC signals.
In the delivery condition, every device has the CFC chart Process mode inactive, that initiates the Group
alarm (see chapter
Life contact
Red error LED
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Device-Diagnosis Log
Device bus error (repeated):
Check the module configuration and the module connections.
Contact the Customer Support Center.
Incorrect hardware configuration:
Synchronize the hardware configuration of the device with DIGSI.
Wrong module 1-12 detected:
Synchronize the hardware configuration of the device with DIGSI.
Identified wrong plug-in module on plug-in module position E/F/M/N/P:
Synchronize the hardware configuration of the device with DIGSI.
Wrong application configuration:
Search for the cause in the operational log and load a valid configuration to the device.
Data-structure error:
Contact the Customer Support Center.
Firmware-version error:
Contact the Customer Support Center.
Signature error:
Contact the Customer Support Center.
CFC error:
In DIGSI, check your CFC chart for the cause.
Binary-output error in module 1 - 12:
Contact the Customer Support Center.
A missing display configuration was established:
Synchronize the hardware configuration of the device with DIGSI.
(_:300) Group alarm is generated and recorded in the operational log.
8.9 Group
Indications).
Is terminated in case of Group alarm
Is initiated in case of Group alarm
Supervision Functions
8.8 Error Responses and Corrective Measures
(_:503) >Group