[scresetu-230213-01.tif, 1, en_US]
Figure 3-20
Use Res. binary outputs to reset stored output contacts.
Actuate the softkey Start in the base bar.
As needed, enter the confirmation ID when requested and then confirm with the softkey Enter.
Use Reset LEDs to reset stored LEDs that are not assigned to a special Function group.
Actuate the softkey Start in the base bar.
As needed, enter the confirmation ID when requested and then confirm with the softkey Enter.
Depending on device configuration, the function group(s) are displayed to you as submenus for which sepa-
rately corresponding, stored LEDs can be reset.
Go to the submenu of the selected function group.
Use Reset LEDs to reset stored LEDs in the selected function group.
Actuate the softkey Start in the base bar.
As needed, enter the confirmation ID when requested and then confirm with the softkey Enter.
Confirmation of Stored Indications via Binary Inputs
Confirmation via entry >LED Reset
Confirmation via binary input >LED-Reset brings about the activation of all LEDs (LED test) and, in case of
dropout of signal, the resetting of all stored indications. Stored LEDs, output contacts and spontaneous fault
messages (display) are reset.
Confirmation of Stored Indications with DIGSI 5
You can confirm stored indications via DIGSI 5 in online operation. For this, go to the project tree.
Select Online access → Interface → Device → Device information.
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Reset Functions on the On-Site Operation Panel
System Functions
3.1 Indications
63