Basic Structure of the Function
2.2 Adjustment of Application Templates/Functional Scope
The current function point consumption can be queried in DIGSI 5 using the menu item Device information
diagram in the tab Resource consumption. The number of function points which functions or function blocks
require is found in
Extending the Function-Point Credit
You can reorder function points if the function-point credit for the device is not enough.
Proceed as follows:
Determine the function point requirement of certain functions, for example, with DIGSI 5 or the
SIPROTEC 5 Configurator
verteilung/schutz/siprotec5/bestellkonfigurator.htm).
Order the additional function points from your local distributor or at http://www.energy.siemens.com.
Siemens will provide you with a signed license file for your device, either via e-mail or for downloading.
Use DIGSI 5 to load the signed license file into your device. The procedure is described in the Online Help
of DIGSI 5.
36
Table
4-1.
(http://www.energy.siemens.com/hq/de/automatisierung/stromuebertragung-
SIPROTEC 5, Fault Recorder, Manual