20-mA Unit Ethernet

6.5.3
6.5.3.1

Overview

The function 20-mA unit Ether.:
Communicates in series with a 20-mA unit via the Slave Unit Protocol (SUP) and records the values meas-
ured by the 20-mA unit
Transforms the measured 20-mA values into slowly changing process tags such as temperature or gas
pressure
Makes the recorded process tags available to CFC, GOOSE, protocols and the device display
Monitors communication with the 20-mA unit
6.5.3.2

Structure of the Function

The function 20-mA unit Ether. can work only in the function group Analog units. A maximum of 4 function
instances can work simultaneously. Each instance contains 12 preconfigured channel function blocks.
The function 20-mA unit Ether. contains input and output channels which can be configured independently
of one another.
[dwstrfn2-150113-01.tif, 2, en_US]
Figure 6-33
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Structure/Embedding of the Function
Function-Group Types
6.5 Function-Group Type Analog Units