Siemens SIPROTEC 5 Manual page 446

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Technical Data
11.6 Operational Measured Values and Statistical Values
Tolerance
Frequency range (expanded)
Tolerance
Reactive power Q
Measuring range
Voltage range
Current range
Frequency range
Tolerance
Frequency range (expanded)
Tolerance
Apparent power S
Measuring range
Voltage range
Current range
Frequency range
Tolerance
Frequency range (expanded)
Tolerance
Frequency
Frequency f
Range
Tolerance
Range
Tolerance
Frequency range (expanded)
Tolerance
Statistical Values of the Device
Device operating hours
Range
Tolerance
446
0.3 % of the measured value in the above mentioned
measuring range
40 Hz to 69 Hz at f
= 50 Hz
rated
50 Hz to 70 Hz at f
= 60 Hz
rated
0.5 % of the measured value in the above mentioned
measuring range
var secondary
|cosφ| ≤ 0.984
(0.8 to 1.2) · V
rated
(0.1 to 2) · I
rated
49 Hz to 51 Hz at f
= 50 Hz
rated
59 Hz to 61 Hz at f
= 60 Hz
rated
1.0 % of the measured value in the above mentioned
measuring range
40 Hz to 69 Hz at f
= 50 Hz
rated
50 Hz to 70 Hz at f
= 60 Hz
rated
1.5 % of the measured value in the above mentioned
measuring range
VA secondary
(0.01 to 2) · S
rated
(0.8 to 1.2) · V
rated
(0.01 to 2) · I
rated
49 Hz to 51 Hz at f
= 50 Hz
rated
59 Hz to 61 Hz at f
= 60 Hz
rated
0.3 % of the measured value in the above mentioned
measuring range
40 Hz to 60 Hz at f
= 50 Hz
rated
50 Hz to 70 Hz at f
= 60 Hz
rated
0.5 % of the measured value in the above mentioned
measuring range
Hz
f
- 0.20 Hz < f
+ 0.20 Hz
rated
rated
± 5 mHz in the V
range
rated
f
- 3.00 Hz < f
+ 3.00 Hz
rated
rated
± 10 mHz in the V
range
rated
25 Hz to 80 Hz; operational measured values
10 Hz to 80 Hz; functional measured values, system
frequency
20 mHz in the range f
± 10 % for rated values
rated
h
0 to 9999999 h
1 h
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siemens 7ke85

Table of Contents