Trigger Management - Siemens SICAM Q100 Device Manual

Power monitoring device and class a power quality recorder
Hide thumbs Also See for SICAM Q100:
Table of Contents

Advertisement

15 Operating Parameters
15.5 Recording and Reporting
15.5.2

Trigger Management

Parameter
Trigger active
Tolerance unit
Lower threshold
Upper threshold
Hysteresis
Detection mode
Trigger active
Tolerance unit
Lower threshold
Upper threshold
Hysteresis
Trigger active
Trigger source
Trigger value
Total recording duration
Pretrigger ratio
Record ph-ph voltage
1)
The detection mode will always synchronize with the setting of Record ph-ph voltage.
352
Default Setting
Voltage trigger limits
no
Percentage
90.00 %
of the nominal/declared
supply voltage
110.00 %
of the nominal/declared
supply voltage
2.00 %
of the nominal/declared
supply voltage
1)
ph-N
Current trigger limits
no
Percentage
90.00 %
of nominal current In
110.00 %
of nominal current In
2.00 %
of nominal current In
Configuration binary trigger
no
Binary Input 1
OFF
Waveform capture setting
2.0 s
10 %
no
Setting Range
no
yes
Percentage
Numerical
0.00 % to 99.99 % of the nominal/declared
supply voltage
0.0 V to 1 000 000.0 V
100.0 % to 10 000.0 % of the nominal/de-
clared supply voltage
0.0 V to 1 000 000.0 V
0.0 % to 50.0 % of the nominal/declared
supply voltage
ph-N
ph-ph
no
yes
Percentage
Numerical
0.00 % to 99.99 % of of nominal current In
0.0 A to 1 000 000.0 A
100.0 % to 10 000.0 % of of nominal
current In
0.0 A to 1 000 000 A
0.0 % to 50.0 % of of nominal current In
no
yes
Indication 1 from Remote
Indication 2 from Remote
Binary Input 1
Binary Input 2
ON
OFF
0.2 s to 3.0 s in 0.2-s steps
0 % to 30 % in 5-% steps
no
yes
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018