Pg-B2 Open-Collector Input Wiring - Sinking Pg - YASKAWA F7 User Manual

Hide thumbs Also See for F7:
Table of Contents

Advertisement

http://www.aotewell.com
Branch
Circuit
Protection
Tel: +(86) 755 8660 6182
Drive
Shielded twisted-pair wires must be used for signal lines.
Do not use the PG-B2's power supply for anything other than the pulse generator (encoder).
Using it for another purpose can cause malfunctions due to noise.
The length of the pulse generator's wiring must not be more than 100 meters.
The direction of rotation of the PG can be set in parameter F1-05 (PG Rotation).
The factory preset is for forward rotation, A-phase advancement.
Fig 2.20 PG-B2 Open-Collector Input Wiring - Sinking PG
Electrical Installation 2 - 35
Aotewell
Power supply +12 V
Power supply 0 V
A-phase pulse open-collector input
B-phase pulse open-collector input
A-phase pulse monitor output
B-phase pulse monitor output
Aotewell
Email: Sales@aotewell.com
http://www.aotewell.com