Checking and Controlling the Installation Site

Install the Drive as described below and maintain optimum conditions.

Installation Site

Install the Drive to a non-combustible surface under the following conditions in UL Pollution Degree 2 environments. This
excludes wet locations where pollution may become conductive due to moisture, and locations containing conductive foreign
matter.
Type
NEMA Type 1
Open Chassis
Protective covers are attached to the top and bottom of the Drive. It is recommended to remove the protective covers before
operating a NEMA Type 1 Drive (Models CIMR-F7U2030/4055 and smaller) in a panel to obtain the 113° (45°C) ambient
operating temperature.
Observe the following precautions when installing the Drive. Make sure to install:
in a clean location which is free from oil mist and dust.
in an environment where metal shavings, oil, water, or other foreign materials do not get into the Drive.
in a location free from radioactive materials and combustible materials (e.g. wood).
in a location free from harmful gases and liquids.
in a location free from excessive vibration.
in a location free from chlorides.
in a location away from direct sunlight.

Controlling the Ambient Temperature

To enhance the reliability of operation, the Drive should be installed in an environment free from extreme temperature
variation. If the Drive is installed in an enclosure, use a cooling fan or air conditioner to maintain the internal air temperature
below 113°
(45°C).
F

Protecting the Drive from Foreign Matter

During Drive installation and project construction, it is possible to have foreign matter such as metal shavings or wire
clippings fall inside the Drive. To prevent foreign matter from falling into the Drive, place a temporary cover over the Drive.
Always remove the temporary cover from the Drive before start-up. Otherwise, ventilation will be reduced, causing the Drive
to overheat.
Tel: +(86) 755 8660 6182
Table 1.3 Installation Site Specifications
Ambient Operating Temperature
14°F-to 104°F (-10-to +40°C)
14°F-to 113°F (-10-to-+45°C)
Physical Installation 1 - 11
Aotewell
95%-RH-or-less-(no-condensation)
95%-RH-or-less-(no-condensation)
Aotewell
Email: Sales@aotewell.com
Humidity