Wire Size For Remote Mount Resistor Unit - YASKAWA F7 User Manual

Hide thumbs Also See for F7:
Table of Contents

Advertisement

http://www.aotewell.com
Remote Mount Resistor Unit Installation Using Internal Braking Transistor
(for F7U20P4 thru F7U2018 and F7U40P4 thru F7U4018)
Since the Remote Mount Resistor Unit generates heat during dynamic braking operation, install it in a location away from
other equipment.
1. Install the Remote Mount Resistor Unit to a noncombustible surface, maintaining a minimum 1.97 inches (50mm)
clearance on each side and a minimum 7.87 inches (200mm) clearance on top.
2. Remove the Remote Mount Resistor Unit cover to access its terminal block. Connect the Remote Mount Resistor Unit to
the Drive and to external control circuitry according to the figure below.
Terminals
Wire Size (AWG)
Wire Type
Terminal Screw
* Power Leads for the Remote Mount Resistor Unit generate high levels of electrical noise - these signal leads must be grouped separately.
Fig 2.6 Wiring Remote Mount Resistor Unit (for F7U20P4 thru F7U2018 and F7U40P4 thru F7U4018)
3. Reinstall and secure Remote Mount Resistor Unit cover and Drive front cover.
4. Proceed to "Adjustments" section on Page 2-18.
Tel: +(86) 755 8660 6182
Aotewell
Table 2.9 Wire Size for Remote Mount Resistor Unit
B, P, R1, R2
12-10
600V Ethylene propylene rubber insulated, or equivalent
S3
SN
120 VAC
Electrical Installation 2 - 14
Aotewell
Email: Sales@aotewell.com
M4
3% DUTY CYCLE
RESISTOR ASSEM-
(R2)*
(R1)*
*
Terminal markings in parentheses
are for resistors manufactured by
Powerohm Resistors Inc.
Applies when SC is jumpered to SP
and S3 is programmed as External
Fault.
http://www.aotewell.com
1, 2*
18-14*
IM

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents