Using Modbus Communication
Serial communication can be performed with Program Logic Controllers (PLCs) or similar master devices using the Modbus
protocol.
Modbus Communication Configuration
Modbus communication is configured using 1 master (PLC) and a maximum of 31 slaves. Serial communication between
master and slave is normally initiated by the master and responded to by the slaves.
The master performs serial communication with one slave at a time. Consequently, the slave address of each slave must be
initially set, so that the master can perform serial communication using that address. Slaves receiving commands from the
master perform the specified functions, and send a response back to the master.
Communication Specifications
The Modbus communication specifications are shown below:
Interface
Communications Cycle
Communications Parameters
Communications Protocol
Number of Connectable Units
Tel: +(86) 755 8660 6182
Master
Fig D.1 Example of Connections between Master and Drive
Table D.1 Modbus Communication Specifications
Item
RS-422, RS-485
Asynchronous (Start-stop synchronization)
Baud rate:
Data length:
Parity:
Stop bits:
Modbus RTU
31 units maximum
Communications D - 2
Aotewell
Slaves
F7
F7
Specifications
Select from 1200, 2400, 4800, 9600, and 19200 bps.
8 bits fixed
Select from even, odd, or none.
1 bit selected