Parameter
Parameter Name
No.
Digital Operator Display
F1-21
PG Constant 2
<3021>
PG Pulse / Rev 2
F1-22
PG Rotation 2
<3021>
PG Rotation Sel 2
H4-02
Terminal FM Gain Setting
Terminal FM Gain
H4-05
Terminal AM Gain Setting
Terminal AM Gain
Motor Overload Protection
L1-01
Selection
MOL Fault Select
Stall Prevention Selection
L3-04
During Decel
StallP Decel Sel
Denotes that parameter can be changed when the Drive is running.
Tel: +(86) 755 8660 6182
Aotewell
Description
Sets the number of pulses for the encoder (pulse generator) for
each full rotation of Motor 2.
Determines the direction of rotation for the encoder (PG) con-
nected to Motor 2.
0: Phase A leads with Forward Run Command.
(Phase B leads with Reverse Run Command.)
1: Phase B leads with Forward Run Command.
(Phase A leads with Reverse Run Command.)
Sets terminal FM output voltage (in percent of 10Vdc) when
selected monitor is at 100% output.
Sets terminal AM output voltage (in percent of 10Vdc) when
selected monitor is at 100% output.
Sets the motor thermal overload protection (OL1) based on the
cooling capacity of the motor.
0: Disabled
1: Standard Fan Cooled (<10:1 motor)
2: Standard Blower Cooled (10:1 motor)
3: Vector Motor (1000:1 motor)
When using a braking resistor, use setting "0". Setting "3" is used
in very specific applications.
0: Disabled - The Drive decelerates at the active deceleration rate.
If the load is too large or the deceleration time is too short, an
OV fault may occur.
1: General Purpose - The Drive decelerates at the active
deceleration rate, but if the main circuit DC bus voltage reaches
the stall prevention level (380/760 Vdc), deceleration will stop.
Deceleration will continue once the DC bus level drops below
the stall prevention level.
2: Intelligent - The active deceleration rate is ignored and the Drive
decelerates as fast as possible w/o hitting OV fault level.
Range: C1-02/10.
3: Stall Prevention w/ Braking Resistor
Start-Up 4 - 14
Aotewell
Email: Sales@aotewell.com
Control Method
Setting
Factory
Range
Setting
V/F
0 to 60000
1024
No
0, 1
0
No
0.0 to
100.0%
Q
1000.0
0.0 to
50.0%
Q
1000.0
0 to 1
1
Q
0 to 3
1
Q
http://www.aotewell.com
V/F
w/
OLV
FV
PG
Q
No
Q
Q
No
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q