V/F Pattern; E1-03 V/F Pattern Selection; Input Voltage Setting - YASKAWA F7 User Manual

Hide thumbs Also See for F7:
Table of Contents

Advertisement

http://www.aotewell.com

Input Voltage Setting

E1-01 Input Voltage Setting
Setting Range:
155.0V to 255.0V (240V Models)
310.0V to 510.0V (480V Models)
Factory Defaults: 230.0V (240V Models)
460.0V (480V Models)
Set the Input Voltage parameter (E1-01) to the nominal voltage of the connected AC power supply. This parameter adjusts the
levels of some protective features of the Drive (i.e. Overvoltage, Built-in Braking Transistor Turn-on, Stall Prevention, etc.).
E1-01 also serves as the Maximum/Base Voltage used by the Preset V/F curves (E1-03=0 to E).
DRIVE INPUT VOLTAGE (NOT MOTOR VOLTAGE) MUST BE SET IN E1-01 FOR THE PRO-
TECTIVE FEATURES OF THE DRIVE TO FUNCTION PROPERLY. FAILURE TO DO SO
MAY RESULT IN EQUIPMENT DAMAGE AND/OR PERSONAL INJURY.

V/F Pattern

E1-03 V/F Pattern Selection

Setting
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
FF
Note: VT = Variable Torque, HST = High Starting Torque
Tel: +(86) 755 8660 6182
Aotewell
WARNING
60Hz (with 50Hz Base)
72Hz (with 60Hz Base)
90Hz (with 60Hz Base)
120Hz (with 60Hz Base)
180Hz (with 60Hz Base)
Custom V/F ( factory default )
Custom w/o limit
Basic Programming 5 - 12
Aotewell
Email: Sales@aotewell.com
Description
50Hz
60Hz
50Hz VT1
50Hz VT2
60Hz VT1
60Hz VT2
50Hz HST1
50Hz HST2
60Hz HST1
60Hz HST2
http://www.aotewell.com

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents