Deceleration To Stop; Coast To Stop - YASKAWA F7 User Manual

Hide thumbs Also See for F7:
Table of Contents

Advertisement

http://www.aotewell.com
When the output frequency has dropped below the DC Injection Start Frequency (b2-01) or the minimum output frequency
(E1-09) (whichever is greater), deceleration will stop and DC current will be injected into the motor at the current level set in
b2-02 for the time set in b2-04.
Run Command
Output Frequency
The actual deceleration time can be determined by the following formula:
IMPORTANT

1: Coast to stop:

When the run command is removed, the Drive will turn off its output transistors. The friction of the driven
equipment will eventually overcome any residual inertia of the system and the motor will stop.
Run Command
Output Frequency
IMPORTANT
Tel: +(86) 755 8660 6182
100 %
Deceleration Time (C1-02)
0 %
Fig 5.3 Deceleration to Stop
Output
frequency
=
Time
to
stop
Maximum
If S-Curve characteristics are set in the Drive programming, they will add to the total time to stop.
100 %
0 %
After a stop is initiated, subsequent run commands will be ignored until the Minimum Baseblock Time
(L2-03) has expired.
Aotewell
at time
of
stop
command
frequency
(E1
04)
Fig 5.4 Coast to Stop
Basic Programming 5 - 6