The grounding surfaces must be highly conductive bare metal. Remove any varnish or paint from grounding surfaces. Be sure
to ground the motor of the machine/application. Line filter and Drive must be mounted on the same metal plate. Mount the two
components as close to each other as possible, with cables kept as short as possible, not exceeding 15.75" (see Fig 2.15). See
Table 2.16 for recommended filters.
EMC Filter
Tel: +(86) 755 8660 6182
Cable
Max. Length: 15.75"
(Remove varnish or paint)
Fig 2.15 EMC Filter Layout
Electrical Installation 2 - 27
Aotewell
Grounding (Remove varnish or paint)
Grounding
Aotewell
Email: Sales@aotewell.com
Motor Cable
Max. Length: 82 feet
IM
http://www.aotewell.com
Metal plate
F7 Drive