480Vac Drive Specifications - YASKAWA F7 User Manual

Hide thumbs Also See for F7:
Table of Contents

Advertisement

http://www.aotewell.com
480Vac
Model Number CIMR-F7U 40P4
Rated output
capacity (kVA)
*2
Horsepower
Rated output current (A)
*3
Overload capacity
(% of rated output
current for 60 sec)
Current limit (% of
rated output current)
*4
Carrier frequency
Maximum output
frequency
Rated output
capacity (kVA)
*2
Horsepower
Rated output current (A)
*3
Overload capacity
(% of rated output
current for 60 sec)
(
Current limit
% of rated
output current)
Carrier frequency (kHz)
Maximum output
frequency
Maximum output voltage
Rated voltage
Rated frequency
Rated input current -
*1
Heavy Duty
(A)
Rated input current -
*1
Normal Duty
(A)
Allowable voltage
fluctuation
Allowable frequency
fluctuation
DC Reactor
Measures
for power
supply
12-pulse
harmonics
Rectification
*1 The difference between Heavy Duty ratings and the Normal Duty ratings for the Drive are the rated input and output current, overload capacity, carrier frequency, current limit,
and maximum output frequency. Parameter C6-01 must be set to value of "0" for Heavy Duty ratings and "2" for Normal Duty ratings. Factory default is Heavy Duty (C6-01=0).
*2 Horsepower ratings are based on 230V or 460V NEC Table 430.150. The maximum applicable motor output is given for a standard 4-pole motor. When selecting the actual
motor and Drive, be sure that the Drive's rated output current is appropriate for the motor's rated current.
*3 Model 2110 has an overload rating of 138% of rated output current for 60 seconds and a current limit rating of 138%. Models 4220 and 4300 have an overload rating of 150%
of rated output current for 45 seconds and a current limit rating of 150%.
*4 When setting the carrier frequency above the factory default, the Drive must be derated.
*5 Heavy Duty ratings for models 2110, 4220 and 4300 are effective in software version VSF103021 and higher.
*6 Each value shown is the Maximum carrier frequency and default carrier frequency.
*7 The carrier frequency for Heavy Duty is default to 2 kHz. Software version VSF103021 and higher may allow the carrier frequency to be increased above 2 kHz with a
reduction in continuous rated output current. Refer to C6-02 in Chapter 5 for further details.
Tel: +(86) 755 8660 6182
Table C.2 480Vac Drive Specifications
40P7
41P5
1.4
1.6
2.8
0.5/0.75
1
2
1.8
2.1
3.7
1.4
1.6
2.8
0.5/0.75
1
2
1.8
2.1
3.7
120
120
120
*5
15
15
15
3-phase; 380, 400, 415, 440, 460, or 480Vac (Proportional to input voltage.)
2.2
2.5
4.4
2.2
2.5
4.4
Aotewell
42P2
43P7
44P0
4.0
5.8
6.6
3
5
-
5.3
7.6
8.7
150
150
2kHz
300.0Hz
4.0
5.8
6.6
3
5
-
5.3
7.6
8.7
120
120
120
120
15
15
15
400.0Hz
3-phase, 380, 400, 415, 440, 460 or 480Vac, 50/60Hz
6.4
9.0
10.4
6.4
9.0
10.4
+ 10%, - 15%
±5%
Optional
Not possible
Specifications C - 3
Aotewell
Email: Sales@aotewell.com
45P5
47P5
4011
9.5
13.0
18.0
7.5
10
15
12.5
17.0
24.0
9.5
13.0
21.0
7.5
10
15/20
12.5
17.0
27.0
120
120
107
15
15
8
15
20
29
15
20
33
http://www.aotewell.com
4015
4018
4022
24.0
30.0
34.0
20
25
30
31.0
39.0
45.0
26.0
30.0
38.0
25
30
-
34.0
40.0
50.4
109
117
107
10
10
10
37
47
50
40
48
55