Parameter
Parameter Name
No.
Digital Operator Display
Terminal M3-M4 Function
H2-02
Selection
Term M3-M4 Sel
Terminal M5-M6 Function
H2-03
Selection
Term M5-M6 Sel
Denotes that parameter can be changed when the Drive is running.
Note: Some digital outputs are control method dependent.
Tel: +(86) 755 8660 6182
Aotewell
Table A.1 F7 Parameter List (Continued)
Description
11: Reset Command Active
Closed = When the Drive receives a reset command from a
digital input terminal or serial communication.
12: Timer Output
Output for independent timer, controlled by b4-01 and b4-02.
Used in conjunction with the digital input H1-
function".
13: Fref/Fout Agree 2
Closed = When Drive output frequency equals the frequency
reference +/- the hysteresis of L4-04.
14: Fref/Set Agree 2
Closed = When the Drive output frequency and the frequency
reference are equal to the value in L4-03 +/- the hysteresis of
L4-04.
15: Frequency Detection 3
Closed = When the Drive output frequency is less than or equal
to the value in L4-03 with the hysteresis determined by L4-04.
16: Frequency Detection 4
Closed = When the Drive output speed is greater than or equal
to the value in L4-03, with the hysteresis determined by L4-04.
17: Torque Detection 1 N.C.
Open = When the output current/torque exceeds the value set in
parameter L6-02 for more time than is set in parameter
L6-03.
18: Torque Detection 2 N.O.
Closed = When the output current/torque exceeds the value set
in parameter L6-05 for more time than is set in parameter
L6-06.
19: Torque Detection 2 N.C.
Open = when the output current/torque exceeds the value set in
parameter L6-05 for more time than is set in parameter L6-06.
1A: Reverse Direction
Closed = When the Drive is running in the reverse direction.
1B: Baseblock 2 N.C.
Open = When Drive is not outputting voltage.
1C: Motor 2 Selection
Closed = When motor 2 is selected by multi-function input
"motor 2 selection".
1D: Regenerating
Closed = When in regenerating mode.
1E: Restart Enabled
Closed = When the Drive is performing an automatic restart
attempt. Automatic restart is configured by parameter L5-01.
1F: Overload (OL1)
Closed = When OL1 function is at 90% of its trip point or
greater.
20: OH Pre-Alarm
Closed = When the Drive's heatsink temperature exceeds the
setting of parameter L8-02.
30: During Torque Limit (when in speed control)
Closed = When in torque limit.
31: During Speed Limit
Closed = When in speed limit.
32: During Speed Limit (when in torque control)
Closed = When motor frequency is at the speed limit value
when running in torque control.
33: Zero-Servo Complete
Closed = When Zero Servo is complete within the b9-02 zero
servo completion width.
36: Frequency Detection 5 <3021>
Closed = When the Drive output speed is greater than or equal
to the value in L4-03, with the hysteresis determined by L4-04.
37: During Run 2
Closed = When Drive is operating (except during baseblock or
DC braking).
38: Drive Enable
Closed = When the Drive enable input is active.
3D: Drive Cooling Fan Fault Detect <3021>
Closed: When drive's cooling fan fault is detected.
Parameters A - 26
Aotewell
Email: Sales@aotewell.com
Setting
Factory
Range
Setting
= 18 "timer
0 to 38
1
0 to 38
2
http://www.aotewell.com
Control Method
Open
V/F
Flux
V/F
Loop
w/PG
Vector
Vector
A
A
A
A
A
A
A
A