Wiring Terminal Blocks
Wire Sizes (Same for All Models)
Terminal wire sizes are shown in Table 2.23.
Terminal
Pulse generator power supply
Pulse input terminal
Pulse monitor output terminal
Shield connection terminal
Wiring Method and Precautions
Observe the following precautions when wiring.
•
Separate the control signal lines for the PG (Encoder) Feedback Board from main circuit lines and power lines.
Connect the shield when connecting a PG (Encoder). The shield must be connected to prevent operational errors
•
caused by noise. Also, do not use any lines that are more than 100m long. Refer to Fig 2.12 for details on
connecting the shield.
•
Do not solder the ends of wires. Doing so may cause contact faults.
When straight solderless terminals are not used, strip the wires to a length of approximately 5.5mm.
•
Use shielded, twisted-pair wires for pulse inputs and pulse output monitor wires, and connect the shield to the shield
•
connection terminal.
Tel: +(86) 755 8660 6182
Aotewell
Table 2.23 Wire Sizes
Wire Thickness
Terminal
Screws
AWG (mm
Stranded wire:
24 to 17 (0.2 to 1.0)
-
Single wire:
24 to 17 (0.2 to 1.0)
M3.5
20 to 16 (0.5 to 1.3)
Electrical Installation 2 - 40
Aotewell
Email: Sales@aotewell.com
2
)
• Shielded, twisted-pair wire
• Shielded, polyethylene-covered, vinyl sheath cable
• Belden 9504, Hitachi KPEV-S, or equivalent
http://www.aotewell.com
Wire Type