Parameter
Parameter Name
No.
Digital Operator Display
H6-04
Pulse Train Input Bias
Pulse Input Bias
H6-05
Pulse Train Input Filter Time
Pulse In Filter
Terminal MP Pulse Train
H6-06
Monitor Selection
Pulse Moni Sel
Pulse Train Monitor
H6-07
Scaling
Pulse Moni Scale
Motor Overload
L1-01
Protection Selection
MOL Fault Select
Motor Overload
L1-02
Protection Time
MOL Time Const
Motor Overheat Alarm
L1-03
Operation Selection
Mtr OH Alarm Sel
Motor Overheat Fault
L1-04
Operation Selection
Mtr OH Fault Sel
Motor Temperature Input
L1-05
Filter Time
Mtr Temp Filter
Momentary Power Loss
L2-01
Detection Selection
PwrL Selection
Momentary Power Loss Ride-
L2-02
thru Time
PwrL Ridethru t
Momentary Power Loss
L2-03
Minimum Base Block Time
PwrL Baseblock t
Momentary Power Loss
L2-04
Voltage Recovery Ramp Time
PwrL V/F Ramp t
Undervoltage Detection
L2-05
Level
PUV Det Level
KEB Deceleration Rate
L2-06
KEB Decel Time
Momentary Recovery Time
L2-07
UV Return Time
Denotes that parameter can be changed when the Drive is running.
Tel: +(86) 755 8660 6182
Aotewell
Table A.1 F7 Parameter List (Continued)
Description
Sets the output level when the pulse train input is 0Hz as a
percentage of maximum output frequency E1-04.
Sets the pulse train input filter time constant in seconds.
Select the pulse train monitor output terminal MP function (value of
the
part of U1-
). See Table A2 for the list of U1
monitors.
Sets the number of output pulses when the monitor is 100% (in Hz).
Set H6-06 to 2, and H6-07 to 0, to make the pulse train
monitor output synchronous to the output frequency.
Motor Overload
Sets the motor thermal overload protection (OL1) based on the
cooling capacity of the motor.
0: Disabled
1: Standard Fan Cooled (< 10:1 motor)
2: Standard Blower Cooled (≥ 10:1 motor)
3: Vector Motor (≤ 1000:1 motor)
Sets the motor thermal overload protection (OL1) time. A larger
L1-02 time will increase the time before an OL1 fault will occur.
Sets operation selection when the motor temperature analog input
(H3-09 = E) exceeds the OH3 alarm level (1.17V)
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
Sets stopping method when the motor temperature analog input
(H3-09 = E) exceeds the OH4 fault level (2.34V).
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
This parameter adjusts the filter on the motor temperature analog
input (H3-09 = E). Increase to add stability, decrease to improve
response.
Power Loss Ridethru
Enables and disables the momentary power loss function.
0: Disabled - Drive trips on (UV1) fault when power is lost.
1: Power Loss Ride Thru Time - Drive will restart if power returns
within the time set in L2-02.*
2: CPU Power Active - Drive will restart if power returns prior to
control power supply shut down.*
* In order for a restart to occur, the run command must be
maintained throughout the ride thru period.
Sets the power loss ride-thru time. This value is dependent on the
capacity of the Drive. Only effective when L2-01 = 1.
Sets the minimum time to wait to allow the residual motor voltage
to decay before the Drive output turns back on during power loss
ride thru. After a power loss, if L2-03 is greater than L2-02,
operation resumes after the time set in L2-03.
Sets the time it takes the output voltage to return to the preset V/F
pattern after speed search (current detection mode) is complete.
Sets the Drive's DC Bus undervoltage trip level. If this is set lower
than the factory setting, additional AC input reactance or DC bus
reactance may be necessary. Consult the factory before changing
this parameter setting.
Sets the time required to decelerate to zero speed when a KEB com-
mand is input from a multi-function input.
Set the time (in seconds) to accelerate to the set speed after
recovery from a momentary power loss. If setting = 0.0, then active
acceleration time is used instead.
Parameters A - 30
Aotewell
Email: Sales@aotewell.com
Control Method
Setting
Factory
V/F
Range
Setting
V/F
w/PG
-100.0 to
0.0%
A
100.0
0.00 to
0.10sec
A
2.00
1, 2, 5,
20, 24,
2
A
31, 36
0 to
1440Hz
A
32000
0 to 3
1
Q
0.1 to
8.0min
A
20.0
0 to 3
3
A
0 to 2
1
A
0.00 to
0.20sec
A
10.00
0 to 2
0
A
Varies
0.0 to
by
A
25.5sec
kVA
Varies
0.1 to
by
A
5.0sec
kVA
Varies
0.0 to
by
A
5.0sec
kVA
150 to
190 Vdc
210
(230V)
A
300 to
380 Vdc
420
(480V)
0.0 to
0.0sec
A
200.0
0.0 to
0.0sec
A
25.5
http://www.aotewell.com
Open
Flux
Loop
Vector
Vector
A
A
A
A
A
A
A
A
A
A
A
A
Q
Q
Q
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A