Accel/Decel Time

C1-01 Acceleration Time 1

C1-02 Deceleration Time 1

Setting Range:
0.0 to 6000.0
Factory Default: 10.0sec
C1-01 (Acceleration Time 1) sets the time to accelerate from zero to maximum output frequency (E1-04). C1-02 (Deceleration
Time 1) sets the time to decelerate from maximum output frequency to zero. C1-01 and C1-02 are the factory default active
accel/decel settings. Alternate accel/decel settings (C1-03 through C1-08) can be activated by multi-function digital inputs
(H1-0
= 7 and 1A), or specified by the switch over frequency (C1-11). See Fig 5.7 below.
Tel: +(86) 755 8660 6182
C1-11
C1-07 Rate
C1-01 Rate
Fig 5.7 Acceleration/deceleration Time Switch Over Frequency
Basic Programming 5 - 8
Aotewell
C1-02 Rate
C1-08 Rate
Aotewell
Email: Sales@aotewell.com
Time