YASKAWA F7 User Manual page 188

Hide thumbs Also See for F7:
Table of Contents

Advertisement

http://www.aotewell.com
Parameter
Parameter Name
No.
Digital Operator Display
Multi-Function Digital Input
Terminal S5
H1-03
Function Selection
Terminal S5 Sel
Multi-Function Digital Input
Terminal S6
H1-04
Function Selection
Terminal S6 Sel
Denotes that parameter can be changed when the Drive is running.
Tel: +(86) 755 8660 6182
Aotewell
Table A.1 F7 Parameter List (Continued)
Description
15: Fast-Stop N.O.
Closed = Drive decelerates using C1-09, regardless of run
command status.
16: Motor 2 Selection
Closed = Motor 2 (E3-
, E4-
Open = Motor 1 (A1-02, E1-
17: Fast-Stop N.C.
Closed = Normal operation
Open = Drive decelerates using C1-09, regardless of run
command status.
18: Timer Function
Input for independent timer, controlled by b4-01 and b4-02.
Used in conjunction with the multi-function digital output
function H2-
= 12 "timer output".
19: PID Disable
Closed = Turns off the PID controller.
1A: Accel / Decel Time Selection 2
Based on status of Accel/Decel Time Selection 1 and 2.
1B: Program Lockout
Closed = All parameter settings can be changed.
Open = Only U1-01 can be changed.
1C: Trim Control Increase
Closed = Increase frequency reference by value in d4-02.
Open = Return to normal frequency reference.
Not effective when Preset References are selected (Multi-step
speed digital inputs are closed). Must be used in conjunction
with Trim Ctrl Decrease.
1D: Trim Control Decrease
Closed = Decrease frequency reference by value in d4-02
Open = Return to normal frequency reference.
Not effective when Preset References are selected (Multi-step
speed digital inputs are closed). Must be used in conjunction
with Trim Ctrl Increase.
1E: Reference Sample Hold
Analog frequency reference is sampled then held at time of
input closure.
20: External Fault, Normally Open, Always Detected, Ramp To
Stop
21: External Fault, Normally Closed, Always Detected, Ramp To
Stop
22: External Fault, Normally Open, During Run, Ramp To Stop
23: External Fault, Normally Closed, During Run, Ramp To Stop
24: External Fault, Normally Open, Always Detected, Coast To
Stop
25: External Fault, Normally Closed, Always Detected, Coast To
Stop
26: External Fault, Normally Open, During Run, Coast To Stop
27: External Fault, Normally Closed, During Run, Coast To Stop
28: External Fault, Normally Open, Always Detected, Fast-Stop
29: External Fault, Normally Closed, Always Detected, Fast-Stop
2A:External Fault, Normally Open, During Run, Fast-Stop
2B:External Fault, Normally Closed, During Run, Fast-Stop
2C:External Fault, Normally Open, Always Detected, Alarm Only
2D:External Fault, Normally Closed, Always Detected, Alarm
Only
2E: External Fault, Normally Open, During Run, Alarm Only
2F: External Fault, Normally Closed, During Run, Alarm Only
(Continued on following page).
Parameters A - 23
Aotewell
Setting
Range
)
, E2-
)
0 to 78
0 to 78
Email: Sales@aotewell.com
Control Method
Factory
V/F
Setting
V/F
w/PG
3:
2-wire
A
A
0:
3-wire
4:
2-wire
A
A
3:
3-wire
http://www.aotewell.com
Open
Flux
Loop
Vector
Vector
A
A
A
A