Transferring Octal Bits (32-Bit Data) - Mitsubishi Electric MELSEC iQ-F FX5 Programming Manual

Instructions, standard functions/function blocks
Hide thumbs Also See for MELSEC iQ-F FX5:

Advertisement

Transferring octal bits (32-bit data)

DPRUN(P)
These instructions handle the device number of (s) and (d) with nibble specification as octal numbers, and transfer data.
Ladder diagram
(s)
(d)
FBD/LD
EN
ENO
s
d
Setting data
■Descriptions, ranges, and data types
Operand
Description
*1
(s)
Nibble specification
(d)
Device number of transfer destination
EN
Execution condition
ENO
Execution result
*1 Make sure that the least significant digit of a specified device number is "0".
■Applicable devices
Operand
Bit
X, Y, M, L, SM,
F, B, SB, S
*1
(s)
*1
(d)
*1 B, SB cannot be used.
Processing details
• Octal bit device  Decimal bit device
(s)
Command
input
DPRUN
K6X0
Octal bit device (X)
X27
M27
M20
M19
M18
Do not change.
Decimal bit device (M)
*1
Word
T, ST, C, D, W,
U\G
SD, SW, R
(d)
X0 to X27  M0 to M7, M10 to M17,M20 to M27
K6M0
X20
X17
X10
M17
M10
M9
M8
Structured text
ENO:=DPRUN(EN,s,d);
ENO:=DPRUNP(EN,s,d);
Range
Data type
32-bit signed binary
32-bit signed binary
Bit
Bit
Double word Indirect
specification
Z
LC
LZ
X7
X6
X5
X4
X3
X2
M7
M6
M5
M4
M3
M2
Data type (label)
ANY32
ANY32
BOOL
BOOL
Constant
Others
K, H
E
$
X1
X0
M1
M0
7 BASIC INSTRUCTIONS