■Applicable devices
Operand
Bit
X, Y, M, L, SM,
F, B, SB, S
(U)
(s1)
(s2)
(d1)
*1
(d2)
(d3)
*1 S cannot be used.
*2 T, ST, and C cannot be used.
■Control data
Device
Item
(s1)+0
Error completion type
(s1)+1
Completion status
(s1)+2
Own station channel
(s1)+3
Target station CPU type
(s1)+4
Target network number
(s1)+5
Target station number
(s1)+6
Not used
(s1)+7
Number of resends
(s1)+8
Arrival monitoring time
(s1)+9
Read data length
(s1)+10
Not used
(s1)+11
Clock set flag
Word
T, ST, C, D, W,
U\G
SD, SW, R
*2
Description
...
b15
b8
b7
b6
0
(1)
(1) Error completion type (bit 7)
Specify whether to set data at completion with an error.
• 0: Do not set data in (s1)+11 and later at completion with an error.
• 1: Set data in (s1)+11 and later at completion with an error.
The instruction completion status is stored.
• 0: Normal
• Other than 0: Error (error code)
Specify the channel to be used by own station.
Specify the CPU type of the target station.
• 0000H: Addressed to target station CPU (control CPU)
• 03D0H: Addressed to control system CPU
• 03D1H: Addressed to standby system CPU
• 03D2H: Addressed to system A CPU
• 03D3H: Addressed to system B CPU
• 03E0H: Addressed to multiple CPU No. 1
• 03E1H: Addressed to multiple CPU No. 2
• 03E2H: Addressed to multiple CPU No. 3
• 03E3H: Addressed to multiple CPU No. 4
• 03FFH: Addressed to target station CPU (control CPU)
Specify the network number (1 to 239) of the target station.
Specify the station number of the target station.
• 125: Master station
• 126: Master operating station
• 1 to 120: Local station, intelligent device station, submaster station
■Before instruction execution
Specify the number of resends to be performed if the instruction is not completed
within the monitoring time specified by (s1)+8.
■At completion of instruction
The number of resends performed (result) is stored.
Specify the monitoring time until completion of processing. If processing is not
completed within the monitoring time, the request is resent by the number of
resends specified in (s1)+7.
• 0: 10 seconds
• 1 to 32767: 1 to 32767 seconds
Specify the number of words to be read.
• 1 to 960 (words)
(When reading data from QnACPU: 1 to 480 (words))
The validity status (valid or invalid) of the data in (s1)+12 and later is stored. Note
that the data in (s1)+12 and later is not cleared even when the instruction is
completed successfully.
• 0: Invalid
• 1: Valid
Double word Indirect
specification
Z
LC
LZ
...
b0
0
12 NETWORK COMMON INSTRUCTION
Constant
Others
(U)
K, H
E
$
Setting range
Set by
0000H
User
0080H
System
1, 2
User
0000H
User
03D0H to 03D3H
03E0H to 03E3H
03FFH
1 to 239
User
1 to 120, 125, 126
User
0 to 15
User/
system
0 to 32767
User
1 to 960
User
System
12.1 Link Dedicated Instructions
12
773