Mitsubishi Electric MELSEC iQ-F FX5 Programming Manual page 733

Instructions, standard functions/function blocks
Hide thumbs Also See for MELSEC iQ-F FX5:

Advertisement

Precautions
• For the nibble of a bit device specified by (s2), specify K1 to K4 in the TOD(P) instruction and K1 to K8 in the DTOD(P)
instruction.
Operation error
Error code
Description
(SD0/SD8067)
2441H
Updating procedure with the unit was not properly completed during the execution of the instruction.
2801H
The unit number specified by (U/H) does not exist.
2823H
The buffer memory number specified by (s1) exceeds the buffer memory area.
The buffer memory number specified by (s1) + the number of transfer points specified by (n) exceeds the buffer memory area.
2820H
The device number specified by (s2) + the number of write data specified by (n) exceeds the corresponding device range.
3056H
Timeout occurred while communicating with the connected units during the execution of the instruction.
3060H
Signal error is detected while accessing the connected units during the execution of the instruction.
3580H
An instruction that cannot be used in an interrupt program is used.
8 APPLICATION INSTRUCTION
8.26 Module Access Instruction