• The table below shows the related devices. The clock data stored in these special registers is updated during the END
processing.
Device
Name
Binary code
SD210
Binary clock data (year)
SD211
Binary clock data (month)
SD212
Binary clock data (day)
SD213
Binary clock data (hour)
SD214
Binary clock data (minute)
SD215
Binary clock data (second)
SD216
Binary clock data (day of the week)
Binary code (FX3 compatible area)
SD8013
Binary clock data (second)
SD8014
Binary clock data (minute)
SD8015
Binary clock data (hour)
SD8016
Binary clock data (day)
SD8017
Binary clock data (month)
SD8018
Binary clock data (year)
SD8019
Binary clock data (day of the week)
Precautions
• These instructions occupy seven points of device starting from device number specified by (d). Make sure that these
devices are not used by other machine controls.
Operation error
Error code
Description
(SD0/SD8067)
2820H
The device range specified by (d) exceeds the corresponding device range.
Description
The year data in the clock data is stored as a four-digit binary code.
The month data in the clock data is stored as a binary code.
The day data in the clock data is stored as a binary code.
The hour data in the clock data is stored as a binary code.
The minute data in the clock data is stored as a binary code.
The second data in the clock data is stored as a binary code.
The day-of-a-week data in the clock data (0: Sunday, 1: Monday, ..., 6: Saturday) is stored as a binary code.
The second data in the clock data is stored as a binary code.
The minute data in the clock data is stored as a binary code.
The hour data in the clock data is stored as a binary code.
The day data in the clock data is stored as a binary code.
The month data in the clock data is stored as a binary code.
The year data in the clock data is stored as a four-digit binary code.
The day-of-a-week data in the clock data (0: Sunday, 1: Monday, ..., 6: Saturday) is stored as a binary code.