Transferring 16-bit block data (65535 points maximum)

BMOV(P)
These instructions block transfer the 16-bit binary data of (n) number of devices starting from the one specified by (s) to the
device specified by (d).
Ladder diagram
(s)
FBD/LD
EN
ENO
s
d
n
Setting data
■Descriptions, ranges, and data types
Operand
Description
(s)
Head device for storing the data to be transferred
(d)
Head number of the transfer-destination device
(n)
Number of transfers
EN
Execution condition
ENO
Execution result
■Applicable devices
Operand
Bit
X, Y, M, L, SM,
F, B, SB, S
(s)
(d)
(n)
7 BASIC INSTRUCTIONS
354
7.7 Data Transfer Instructions
(d)
(n)
Word
T, ST, C, D, W,
U\G
SD, SW, R
Structured text
ENO:=BMOV(EN,s,n,d);
ENO:=BMOVP(EN,s,n,d);
Range
1 to 65535
Double word Indirect
specification
Z
LC
LZ
Data type
Data type (label)
16-bit signed binary/
ANY16
32-bit signed binary
16-bit signed binary/
ANY16
32-bit signed binary
16-bit unsigned binary
ANY16
Bit
BOOL
Bit
BOOL
Constant
K, H
E
$
Others