6
PROGRAMMING

6.2 Cyclic Transmission

6.2.1 32-bit data assurance

6 - 7
Depending on the timing of the link refresh, 32-bit (2-word) type link data may be
broken up into new and old data in units of 16 bits (one word).
• Current values of analog-digital converter module
• Current values of positioning module, command speed.
The remote I/O network provides the following functions for making handling of the link
data easy.
• 32-bit data assurance
• Block data assurance per station of cyclic
data
32-bit data precision is guaranteed automatically by setting parameters so that the
following conditions 1) to 4) are satisfied.
If conditions 1) to 4) are not satisfied, a warning for 32-bit data separation is displayed
during setting with GX Developer.
1)
The start device number of LB is a multiple of 20
2)
The number of assigned LB points per station is a multiple of 20
3)
The start device number of LW is a multiple of 2.
4)
The number of assigned LW points per station is a multiple of 2.
Parameter settings for network range assignments
Refreshing link devices that satisfy the above conditions 1) to 4) guarantees
consistency of 32-bit data.
POINT
To guarantee data larger than 32 bits (2 words), use the station unit block
assurance in Section 6.2.2.