13
CC-LINK IE FIELD NETWORK INSTRUCTION
13.1
Setting parameters
G(P).CCPASET
Set the parameters to the FX5-CCLIEF.
Ladder diagram
(U)
FBD/LD
EN
ENO
Un
d
s1
s2
s3
s4
("G_CCPASET", "GP_CCPASET" enters .)
Setting data
■Descriptions, ranges, and data types
Operand
Description
(U)9
Position number of the module connected
(s1)
Own station head device where control data is stored
(s2)
Dummy device
(s3)
Dummy device
(s4)
Dummy device
(d)
Own station device to be turned on for one scan when the
instruction completes.
If the instruction is completed with an error, (d)+1 is also
turned on.
EN
Execution condition
ENO
Execution result
*1 In the case of the ST language and the FBD/LD language, U displays as Un.
*2 Since the operands (s2) to (s4) are not used for the FX5-CCLIEF, specify dummy devices.
■Applicable devices
Operand
Bit
X, Y, M, L, SM,
F, B, SB, S
(U)
(s1)
(s2)
(s3)
(s4)
*1
(d)
*1 S cannot be used.
*2 T, ST, and C cannot be used.
13 CC-LINK IE FIELD NETWORK INSTRUCTION
798
13.1 Setting parameters
(d)
(s1)
(s2)
(s3)
(s4)
*2
*2
*2
Word
T, ST, C, D, W,
SD, SW, R
*2
Structured text
ENO:=G_CCPASET(EN,Un,s1,s2,s3,s4,d);
ENO:=GP_CCPASET(EN,Un,s1,s2,s3,s4,d);
Range
1H to 10H
Refer to Page 799 Control
data.
Double word Indirect
U\G
Z
LC
Data type
16-bit unsigned binary
Device name
Device name
Device name
Device name
Bit
Bit
Bit
Constant
specification
LZ
K, H
Data type (label)
ANY16
ANY16
ANY16
ANY16
ANY16
ANYBIT_ARRAY
(Number of elements:
2)
BOOL
BOOL